Relay

Automotive-style miniature relay, dust cover removed

A relay is an electrically operated switch. Many relays use an electromagnet to operate a switching mechanism, but other operating principles are also used. Relays find applications where it is necessary to control a circuit by a low-power signal, or where several circuits must be controlled by one signal. The first relays were used in long distance telegraph circuits, repeating the signal coming in from one circuit and re-transmitting it to another. Relays found extensive use in telephone exchanges and early computers to perform logical operations. A type of relay that can handle the high power required to directly drive an electric motor is called a contactor. Solid-state relays control power circuits with no moving parts, instead using a semiconductor device to perform switching. Relays with calibrated operating characteristics and sometimes multiple operating coils are used to protect electrical circuits from overload or faults; in modern electric power systems these functions are performed by digital instruments still called "protection relays".

Contents

Basic design and operation

Simple electromechanical relay
Small relay as used in electronics

A simple electromagnetic relay consists of a coil of wire surrounding a soft iron core, an iron yoke, which provides a low reluctance path for magnetic flux, a movable iron armature, and a set, or sets, of contacts; two in the relay pictured. The armature is hinged to the yoke and mechanically linked to a moving contact or contacts. It is held in place by a spring so that when the relay is de-energized there is an air gap in the magnetic circuit. In this condition, one of the two sets of contacts in the relay pictured is closed, and the other set is open. Other relays may have more or fewer sets of contacts depending on their function. The relay in the picture also has a wire connecting the armature to the yoke. This ensures continuity of the circuit between the moving contacts on the armature, and the circuit track on the printed circuit board (PCB) via the yoke, which is soldered to the PCB.

When an electric current is passed through the coil, the resulting magnetic field attracts the armature, and the consequent movement of the movable contact or contacts either makes or breaks a connection with a fixed contact. If the set of contacts was closed when the relay was de-energized, then the movement opens the contacts and breaks the connection, and vice versa if the contacts were open. When the current to the coil is switched off, the armature is returned by a force, approximately half as strong as the magnetic force, to its relaxed position. Usually this force is provided by a spring, but gravity is also used commonly in industrial motor starters. Most relays are manufactured to operate quickly. In a low voltage application, this is to reduce noise. In a high voltage or high current application, this is to reduce arcing.

When the coil is energized with direct current, a diode is often placed across the coil to dissipate the energy from the collapsing magnetic field at deactivation, which would otherwise generate a voltage spike dangerous to circuit components. Some automotive relays already include a diode inside the relay case. Alternatively a contact protection network, consisting of a capacitor and resistor in series, may absorb the surge. If the coil is designed to be energized with alternating current (AC), a small copper ring can be crimped to the end of the solenoid. This "shading ring" creates a small out-of-phase current, which increases the minimum pull on the armature during the AC cycle.[1]

By analogy with functions of the original electromagnetic device, a solid-state relay is made with a thyristor or other solid-state switching device. To achieve electrical isolation an optocoupler can be used which is a light-emitting diode (LED) coupled with a photo transistor.

Types

Latching relay

Latching relay, dust cover removed, showing pawl and ratchet mechanism. The ratchet operates a cam, which raises and lowers the moving contact arm, seen edge-on just below it. The moving and fixed contacts are visible at the left side of the image.

A latching relay has two relaxed states (bistable). These are also called "impulse", "keep", or "stay" relays. When the current is switched off, the relay remains in its last state. This is achieved with a solenoid operating a ratchet and cam mechanism, or by having two opposing coils with an over-center spring or permanent magnet to hold the armature and contacts in position while the coil is relaxed, or with a remanent core. In the ratchet and cam example, the first pulse to the coil turns the relay on and the second pulse turns it off. In the two coil example, a pulse to one coil turns the relay on and a pulse to the opposite coil turns the relay off. This type of relay has the advantage that it consumes power only for an instant, while it is being switched, and it retains its last setting across a power outage. A remanent core latching relay requires a current pulse of opposite polarity to make it change state.

Reed relay

A reed relay has a set of contacts inside a vacuum or inert gas filled glass tube, which protects the contacts against atmospheric corrosion. The contacts are closed by a magnetic field generated when current passes through a coil around the glass tube. Reed relays are capable of faster switching speeds than larger types of relays, but have low switch current and voltage ratings.

Top, middle: reed switches, bottom: reed relay

Mercury-wetted relay

A mercury-wetted reed relay is a form of reed relay in which the contacts are wetted with mercury. Such relays are used to switch low-voltage signals (one volt or less) because of their low contact resistance, or for high-speed counting and timing applications where the mercury eliminates contact bounce. Mercury wetted relays are position-sensitive and must be mounted vertically to work properly. Because of the toxicity and expense of liquid mercury, these relays are rarely specified for new equipment. See also mercury switch.

Polarized relay

A polarized relay placed the armature between the poles of a permanent magnet to increase sensitivity. Polarized relays were used in middle 20th Century telephone exchanges to detect faint pulses and correct telegraphic distortion. The poles were on screws, so a technician could first adjust them for maximum sensitivity and then apply a bias spring to set the critical current that would operate the relay.

Machine tool relay

A machine tool relay is a type standardized for industrial control of machine tools, transfer machines, and other sequential control. They are characterized by a large number of contacts (sometimes extendable in the field) which are easily converted from normally-open to normally-closed status, easily replaceable coils, and a form factor that allows compactly installing many relays in a control panel. Although such relays once were the backbone of automation in such industries as automobile assembly, the programmable logic controller (PLC) mostly displaced the machine tool relay from sequential control applications.

Contactor relay

A contactor is a very heavy-duty relay used for switching electric motors and lighting loads, although contactors are not generally called relays. Continuous current ratings for common contactors range from 10 amps to several hundred amps. High-current contacts are made with alloys containing silver. The unavoidable arcing causes the contacts to oxidize; however, silver oxide is still a good conductor.[2] Such devices are often used for motor starters. A motor starter is a contactor with overload protection devices attached. The overload sensing devices are a form of heat operated relay where a coil heats a bi-metal strip, or where a solder pot melts, releasing a spring to operate auxiliary contacts. These auxiliary contacts are in series with the coil. If the overload senses excess current in the load, the coil is de-energized. Contactor relays can be extremely loud to operate, making them unfit for use where noise is a chief concern.

Solid-state relay

Solid state relay, which has no moving parts
25 A or 40 A solid state contactors

A solid state relay (SSR) is a solid state electronic component that provides a similar function to an electromechanical relay but does not have any moving components, increasing long-term reliability. With early SSR's, the tradeoff came from the fact that every transistor has a small voltage drop across it. This voltage drop limited the amount of current a given SSR could handle. As transistors improved, higher current SSR's, able to handle 100 to 1,200 Amperes, have become commercially available. Compared to electromagnetic relays, they may be falsely triggered by transients.

Solid state contactor relay

A solid state contactor is a heavy-duty solid state relay, including the necessary heat sink, used for switching electric heaters, small electric motors and lighting loads; where frequent on/off cycles are required. There are no moving parts to wear out and there is no contact bounce due to vibration. They are activated by AC control signals or DC control signals from Programmable logic controller (PLCs), PCs, Transistor-transistor logic (TTL) sources, or other microprocessor and microcontroller controls.

Buchholz relay

A Buchholz relay is a safety device sensing the accumulation of gas in large oil-filled transformers, which will alarm on slow accumulation of gas or shut down the transformer if gas is produced rapidly in the transformer oil.

Forced-guided contacts relay

A forced-guided contacts relay has relay contacts that are mechanically linked together, so that when the relay coil is energized or de-energized, all of the linked contacts move together. If one set of contacts in the relay becomes immobilized, no other contact of the same relay will be able to move. The function of forced-guided contacts is to enable the safety circuit to check the status of the relay. Forced-guided contacts are also known as "positive-guided contacts", "captive contacts", "locked contacts", or "safety relays".

Overload protection relay

Electric motors need overcurrent protection to prevent damage from over-loading the motor, or to protect against short circuits in connecting cables or internal faults in the motor windings.[3] One type of electric motor overload protection relay is operated by a heating element in series with the electric motor. The heat generated by the motor current heats a bimetallic strip or melts solder, releasing a spring to operate contacts. Where the overload relay is exposed to the same environment as the motor, a useful though crude compensation for motor ambient temperature is provided.

Pole and throw

Circuit symbols of relays. (C denotes the common terminal in SPDT and DPDT types.)

Since relays are switches, the terminology applied to switches is also applied to relays. A relay will switch one or more poles, each of whose contacts can be thrown by energizing the coil in one of three ways:

The following designations are commonly encountered:

The "S" or "D" may be replaced with a number, indicating multiple switches connected to a single actuator. For example 4PDT indicates a four pole double throw relay (with 14 terminals).

EN 50005 are among applicable standards for relay terminal numbering; a typical EN 50005-compliant SPDT relay's terminals would be numbered 11, 12, 14, A1 and A2 for the C, NC, NO, and coil connections, respectively.

Applications

Relays are used to and for:

A DPDT AC coil relay with "ice cube" packaging

Relay application considerations

A large relay with two coils and many sets of contacts, used in an old telephone switching system.
Several 30-contact relays in "Connector" circuits in mid 20th century 1XB switch and 5XB switch telephone exchanges; cover removed on one

Selection of an appropriate relay for a particular application requires evaluation of many different factors:

Protective relay

A protective relay is a complex electromechanical apparatus, often with more than one coil, designed to calculate operating conditions on an electrical circuit and trip circuit breakers when a fault is detected. Unlike switching type relays with fixed and usually ill-defined operating voltage thresholds and operating times, protective relays have well-established, selectable, time/current (or other operating parameter) curves. Such relays may be elaborate, using arrays of induction disks, shaded-pole magnets, operating and restraint coils, solenoid-type operators, telephone-relay style contacts, and phase-shifting networks. Protection relays respond to such conditions as over-current, over-voltage, reverse power flow, over- and under- frequency, and even distance relays that would trip for faults up to a certain distance away from a substation but not beyond that point. An important transmission line or generator unit will have cubicles dedicated to protection, with a score of individual electromechanical devices. The various protective functions available on a given relay are denoted by standard ANSI Device Numbers. For example, a relay including function 51 would be a timed overcurrent protective relay.

Design and theory of these protective devices is an important part of the education of an electrical engineer who specializes in power systems. Today these devices are nearly entirely replaced (in new designs) with microprocessor-based instruments (numerical relays) that emulate their electromechanical ancestors with great precision and convenience in application. By combining several functions in one case, numerical relays also save capital cost and maintenance cost over electromechanical relays. However, due to their very long life span, tens of thousands of these "silent sentinels" are still protecting transmission lines and electrical apparatus all over the world.

Overcurrent relay

An "overcurrent relay" is a type of protective relay which operates when the load current exceeds a preset value. The ANSI device number is 50 for an instantaneous over current (IOC), 51 for a time over current (TOC). In a typical application the overcurrent relay is connected to a current transformer and calibrated to operate at or above a specific current level. When the relay operates, one or more contacts will operate and energize to trip (open) a circuit breaker.

Induction disc overcurrent relay

These robust and reliable electromagnetic relays use the induction principle discovered by Ferraris in the late 19th century. The magnetic system in induction disc overcurrent relays is designed to detect overcurrents in a power system and operate with a pre determined time delay when certain overcurrent limits have been reached. In order to operate, the magnetic system in the relays produces rotational torque that acts on a metal disc to make contact, according to the following basic current/torque equation:

T  =  K  \times  \phi_1  \times  \phi_2  \sin \theta

Where

K – is a constant

\phi_1 and \phi_2 are the two fluxes

\theta is the phase angle between the fluxes

The relay's primary winding is supplied from the power systems current transformer via a plug bridge, which is also commonly known as the plug setting multiplier (psm). The variations in the current setting are usually seven equally spaced tappings or operating bands that determine the relays sensitivity. The primary winding is located on the upper electromagnet. The secondary winding has connections on the upper electromagnet that are energised from the primary winding and connected to the lower electromagnet. Once the upper and lower electromagnets are energised they produce eddy currents that are induced onto the metal disc and flow through the flux paths. This relationship of eddy currents and fluxes creates rotational torque proportional to the input current of the primary winding, due to the two flux paths been out of phase by 90º.

Therefore in an overcurrent condition a value of current will be reached that overcomes the control spring pressure on the spindle and the breaking magnet causing the metal disc to rotate moving towards the fixed contact. This initial movement of the disc is also held off to a critical positive value of current by small slots that are often cut into the side of the disc. The time taken for rotation to make the contacts is not only dependent on current but also the spindle backstop position, known as the time multiplier (tm). The time multiplier is divided into 10 linear divisions of the full rotation time.

Providing the relay is free from dirt, the metal disc and the spindle with its contact will reach the fixed contact, thus sending a signal to trip and isolate the circuit, within its designed time and current specifications. Drop off current of the relay is much lower than its operating value, and once reached the relay will be reset in a reverse motion by the pressure of the control spring governed by the braking magnet.

Distance relay

The most common form of protection on high voltage transmission systems is distance relay protection. Power lines have set impedance per kilometre and using this value and comparing voltage and current the distance to a fault can be determined. The ANSI standard device number for a distance relay is 21.

Current Differential Protection

Another common form of protection for high voltage apparatus such as transformers and power lines is current differential. This type of protection works on the basic theory of Kirchhoff's current law which states that the sum of the currents entering a node will equal zero. It is important to note the direction of the currents as well as the magnitude as they are vectors. It requires a set of current transformers(smaller transformers that transform currents down to a level which can be measured) at each end of the power line or each side of the transformer. The current protection relay then compares the currents and calculates the difference between the two. As an example a power line from one substation to another will have a current diff relay at both substations which communicate with each other. In a healthy condition relay at substation A may read 500 amps (power exporting) and substation B will read 500 amps (power importing). If a path to earth or groud develops there will be a surge of current. As supply grids are generally well interconnected the fault in the previous example will be fed from both ends of the power line. The relay at substation A will see a massive increase in current and will continue to export. Substation B will also see a massive increase in current however it will now start to export as well. In turn the protection relay will see the currents travelling in opposite directions (180 degrees phase shift) and instead of cancelling each other out to give a summation of zero it will see a large value of current. The relays will trip the associated circuit breakers. this type of protection is called unit protection as it only protects what is between the current transformers. It is important to note that generally the higher the currents in the lines the larger the diff current required for the relay to see it as a fault. this is basically done due to small miss matches in current transformers, small errors will increase as current increases to the point where the error could cause a false trip if the current diff relay only had an upper limit instead of the rising diff characteristic. It is also important to note that CTs have a point where the core saturates and the current in the CT is no longer proportional to the current in the line. A ct can become inaccurate or even saturate because of a fault outside of it s protected zone (through fault) where the cts see a large magnitude but still in the same direction.

Railway signalling

Part of a relay interlocking using miniature plug-in relays
UK Q-style signalling relay and base

General

Railway signalling relays are very big and cumbersome compared to the mostly small voltages (less than 120 V) and currents (perhaps 100 mA) that they switch. Contacts are widely spaced to prevent dangerous flashovers and short circuits over a lifetime that may exceed fifty years.

BR930 series plug-in relays are widely used on railways following British practice. These are 120 mm high, 180 mm deep and 56 mm wide and weigh about 1400 g, and can have up to 16 separate contacts.

Double switching

In railway signalling, relays energise to give a green light, so that if the power fails or a wire breaks, the signal goes to red. This is called "fail-safe". To protect against false feeds relay circuits are often cut on both the positive and negative side, so that two false feeds are needed to cause a false green.

Proving

In railway signalling, many relays are proved down before a signal is allowed to show green. For example, before a points normal detector is allowed to pick up (and allow that signal to show green) the corresponding points reverse detector must be proved in the de-energized position. Not all relays can be proved, for example repeat relays in distant locations, so there is reliance on other features such as carbon to silver contacts to resist lightning induced contact welding and to provide AC immunity.

See also

References

  1. Mason, C. R., Art & Science of Protective Relaying, Chapter 2, GE Consumer & Electrical [1]
  2. Kenneth B. Rexford and Peter R. Giuliani (2002). Electrical control for machines (6th ed.). Cengage Learning. p. 58. ISBN 9780766861985. http://books.google.com/books?id=5RkbwbYq1joC&pg=PA58&lpg=PA58&dq=silver-oxide+relay+contact&source=bl&ots=P4QvEFgf8M&sig=XcF_4ed6DvucJvwck6Q4fxIKjEM&hl=en&ei=8yHlSqH5H4SsswOM6rmwBA&sa=X&oi=book_result&ct=result&resnum=2&ved=0CBAQ6AEwAQ#v=onepage&q=silver-oxide%20relay%20contact&f=false. 
  3. Zocholl, Stan (2003). AC Motor Protection. Schweitzer Engineering Laboratories, Inc.. ISBN 0972502610, 978-0972502610. 
  • Gurevich, Vladimir (2005). Electrical Relays: Principles and Applications. London - New York: CRC Press. 
  • Westinghouse Corporation (1976). Applied Protective Relaying. Westinghouse Corporation. Library of Congress card no. 76-8060. 
  • Terrell Croft and Wilford Summers (ed) (1987). American Electricians' Handbook, Eleventh Edition. New York: McGraw Hill. ISBN 0-07-013932-6. 
  • Walter A. Elmore. Protective Relaying Theory and Applications. Marcel Dekker, Inc.. ISBN 0-8247-9152-5. 
  • Vladimir Gurevich (2008). Electronic Devices on Discrete Components for Industrial and Power Engineering. London - New York: CRC Press. pp. 418. 
  • Vladimir Gurevich (2003). Protection Devices and Systems for High-Voltage Applications. London - New York: CRC Press. pp. 292. 